Lake Geneva, Wisconsin Building Codes

Updated : 04/22/2024

Overview

The village of Lake Geneva, Wi. adopted the Wisconsin Administrative Code including all the provisions that apply to the regulation of construction for both residential and commercial buildings (UDC and CBC). Lake Geneva, Wi. Muni. Code § 14-31 (accessed 4/13/2015). The village also adopted the Wisconsin Uniform Building Code with amendments. Lake Geneva, Wi. Mun. Code § 14.32 (accessed 4/9/2015). “The adoption of this Code is intended to provide the Building Inspector with more specific information in areas where the Wisconsin Administrative Code provides only general guidelines or where no provision exists”. Id. Generally, this code governs regulations that apply to alterations, additions or repairs to existing buildings.

 

The village also adopted the adopted the WAC fire prevention, all of its referenced standards, and the most current NFPA 1 publication as part of its own Fire Code. Lake Geneva, Wi. Mun. Code § 30.01 (adopted) (accessed 4/9/2015). 

 

14.33 – Scope of Article. – “The codes adopted in this article apply to construction and inspection procedures used for all construction of new buildings and additions to or alterations of existing buildings.” This definition applies to both commercial and residential buildings and for dwellings built prior to 1980. Lake Geneva, Wi. Mun. Code § 14.33 (accessed 4/9/2015).

Helpful resources for Lake Geneva, Wisconsin include the following.

Residential Building Code

Wisconsin adopted a statewide mandatory residential code that will control. Authority for local amendments will be limited.See PLRB, Wisconsin Building Codes for more information on state level codes.

Lake Geneva adopted the Wisconsin Uniform Residential CodeYou can find a copy of the code here.You can find information about the adoption without amendment to the model code here.

Auto Search - beta:

Wisconsin Uniform Dwelling Code(City of Lake Geneva , WI Municipal Code)

...Adoption not found...

Drip Edge

Drip Edge: No

Ice Barrier

Comments

The village of Lake Geneva, Wi. adopted the Wisconsin Administrative Code including all the provisions that apply to the regulation of construction for both residential and commercial buildings (UDC and CBC). Lake Geneva, Wi. Muni. Code § 14-31 (accessed 4/13/2015). The village also adopted the Wisconsin Uniform Building Code with amendments. Lake Geneva, Wi. Mun. Code § 14.32 (accessed 4/9/2015). “The adoption of this Code is intended to provide the Building Inspector with more specific information in areas where the Wisconsin Administrative Code provides only general guidelines or where no provision exists”. Id. Generally, this code governs regulations that apply to alterations, additions or repairs to existing buildings.

Existing Buildings

Existing buildings, meaning buildings that were built in accordance to code at the time of construction, typically merit extra consideration in a current updated code.

14.33 – Scope of Article. – “The codes adopted in this article apply to construction and inspection procedures used for all construction of new buildings and additions to or alterations of existing buildings.” This definition applies to both commercial and residential buildings and for dwellings built prior to 1980. Lake Geneva, Wi. Mun. Code § 14.33 (accessed 4/9/2015).

 

Wisconsin Uniform Building Code § 30.03 (3-4.) – Existing Buildings, alterations, and repairs. These sections outline provisions for existing buildings, alterations, and repairs. 

Commercial Building Code

Lake Geneva adopted the 2009 IBC, statewide. Note that adoptions usually come with amendments. So, it is important to review those amendments in addition to the unamended model code.

You can find a copy of the code here.You can find information about the adoption without amendment to the model code here.

Auto Search - beta:

. Wisconsin Commercial Bldg. Code (2015 IBC)(City of Lake Geneva , WI Municipal Code)

...Adoption not found...

Comments

The village of Lake Geneva, Wi. adopted the Wisconsin Administrative Code including all the provisions that apply to the regulation of construction for both residential and commercial buildings (UDC and CBC). Lake Geneva, Wi. Muni. Code § 14-31 (accessed 4/13/2015). The village also adopted the Wisconsin Uniform Building Code with amendments. Lake Geneva, Wi. Mun. Code § 14.32 (accessed 4/9/2015). “The adoption of this Code is intended to provide the Building Inspector with more specific information in areas where the Wisconsin Administrative Code provides only general guidelines or where no provision exists”. Id. Generally, this code governs regulations that apply to alterations, additions or repairs to existing buildings. The statewide CBC includes the 2009 ICC codes (IBC, IEBC, IFGC, IECC, and IMC).

 

The village provides certain grandfathered ordinances (variances to the CBC). An ordinance that is grandfathered has passed the requirements laid out by the Legislature in Wisconsin Statute § 101.02(7r)(b). The grandfathered ordinances are listed below:

 

ARTICLE II. AUTOMATIC SPRINKLER SYSTEMS

 

Sec. 30-3 2. Buildings requiring installation.

 

(a) This article requires the installation of an automatic fire sprinkler system in the following buildings:

(3) Government buildings;

 

(b) A complete approved automatic fire sprinkler protection system shall be provided in all the buildings listed in subsection (a) of this section, except multifamily, as follows:

(1) Fire-resistive buildings. Throughout every building which is either:

a Ten thousand square feet or more in total area;

b. Is over one story in height and exceeds 6,ooo square feet in total area; or

c. Is over two stories in height.

 

(2) Nonfire-resistive buildings. Throughout every building which is either:

a Five thousand square feet or more in total area; or

b. Is over two stories in height.

 

Sec. 30-33. Accessory buildings and special principal building areas.

 

Approved automatic sprinkler equipment shalI be installed and maintained in the following accessory buildings and special principal building areas as follows:

(1) Garages. Automatic sprinkler equipment shall be installed in garages as follows:

a. Garages within, attached to above or below other occupancies.

b. Garages used as passenger terminals.

 

(2) Basements and subbasements. In the basements and subbasements of principal and accessory buildings approved automatic sprinkler equipment shall be installed as follows:

b. All subbasements regardless of size.

 

(4) Daycare centers, including adult day care centers. All buildings in day care centers and adult day care centers, regard less of size, shall have complete sprinkler protection throughout.

(5) Community based residential facilities (CBRF). All buildings in community based residential facilities (CBRF), regardless of size, shall have sprinkler protection throughout.

(6) Theaters and assembly buildings. All buildings in theaters and assembly buildings, regardless of size, shall have sprinkler protection throughout.

(7) Hospitals, nursing, convalescent, old age and other similar Institutional buildings. All buildings of nonfire-resistive construction in hospitals, nursing, convalescent, old age and other similar institutional buildings, regardless of size, shall have sprinkler protection throughout.

(8) Schools, colleges and universities. All buildings of nonfire-resistive construction in schools, colleges and universities, regardless of size, shall have sprinkler protection throughout.

(9) Dormitories, fraternities and sorority houses. All buildings in dormitories, fraternities and sorority houses, regardless of size, shall have sprinkler protection throughout.

(10) Hotels, motels and roominghouses. All buildings of nonfire-resistive construction in hotels, motels and roominghouses, regardless of size, shall have sprinkler protection throughout.

(11) Commercial, industrial and institutional garages and service centers. Any building with a total area of 3,000 square feet in area or greater in commercial, industrial and institutional garages and service centers, regardless of size, shall have sprinkler protection throughout.

 

Sec. 30-34. High-hazard occupancies.

 

(a) Approved automatic fire suppression equipment shall be installed and maintained in the following buildings, regardless of size, in which it is expected there will be high-hazard occupancy, including, but not limited to:

(1) Aircraft hangars.

(2) Dry cleaning establishments using or storing gasoline or other volatile flammable liquids.

(3) Enameling or Japanning operations.

(4) Mills: sugar, starch, cereal, feed, hay flour and grist mills.

(5) Paint and varnish: Manufacturing, storing, handling, spraying, and other related operations.

(6) Paint stripping establishments.

(7) Manufacture and storage of Pyroxylin products.

(8) Smoke houses.

(9) Storage of explosive gages under pressure (15 psi and over 5,400 cubic feet) such as acetylene, hydrogen and natural gas.

(10) Storage of materials with a flashpoint under 200° F., such as celluloid products, kerosene, etc.

(11) Woodworking and other such establishments with combustible dust.

(12) Chemical works and for storage facilities.

(13) Explosive and pyrotechnics manufacturing.

(14) Oil refineries.

 

(b) This article applies to all new construction after the effective date of the ordinance from which this section is derived.

 

Sec. 30-42. Additions or change of use.

 

All existing public, commercial and industrial buildings 6,ooo square feet or more in size, exterior wall dimensions, shall conform to this article. If life occupancy is present in any such structure, this article will apply regardless of size as follows:

(1) Application of article. This article applies to, but is not limited to, places of employment, schools and municipal, state and federal government structures.

(4) Incremental additions. In the event of incremental periodic additions to an existing structure any such additions from the effective date of the ordinance from which this article is derived shall be added together (gross area) and when any such additions total at least 253 of the gross area of the original structure this article and its requirements shall apply to all additions added from the effective date of this ordinance from which this article is derived.

(5) Change of use. If the use of an existing public, commercial or industrial building is changed to any new use the building shall be made to comply with this article. Hotels, motels and other similar buildings, if converted to condominiums or other private ownership, shall be made to comply with the requirements of this article.

 

ARTICLE V. FIRE ALARM SYSTEMS

 

Sec. 30-119. Applicability.

 

These requirements of this article shall apply to all new buildings within the inspection boundaries of the city fire department.

(1) New buildings should comply with the requirement of this article before the building is occupied or used for any purpose other than its construction.

(2) False alarms provisions shall apply to both new and existing structures.

(3) All cost associated with the installation, operation, transmission, and maintenance of automatic fire alarm systems shall be borne by the building owner and/or occupant.

 

Sec. 30-120. Amendments.

 

The codes adopted in section 30-118 of this article are hereby amended as follows:

(1) Transmission of alarm signals:

a. All alarm signals emanating from automatic fire alarm systems shall transmit by dedicated circuit.

b. Non-required systems may transmit clear signals via digital communicator with a daily test signal or other means to a UL listed central station. All alarm signals received by the central station must be relayed to the city fire department alarm center via public switched telephone network at (414) 248-4434 or at said number as established from time to time. A copy of the current UL listing for central station alarm receiving locations shall be on file at the city fire department Alarm installation company shall provide for current UL listing for central stations. Note: After September 25. i999, the area code will change to (262).

c. Systems that transmit alarm via recorder or digital voices shall be prohibited. No fire alarm system shall be programmed to directly dial 911 or other emergency and/or non-emergency number of the city fire department.

 

(4) Zoning of fire alarm systems: Shall be, per NFPA 72, 1-5-7.

(5) Additional specific system requirements:

a. All fire alarm control panels shall be capable of silencing the audio notification signal without re-setting the panel. The silencing switch shall be a single switch requiring no keys, access codes or special knowledge. The re-set switch shall be a single switch requiring no keys, access codes or special knowledge. A key may be used to actuate a remote annunciator panel to silence a system.

c. All smoke detectors should have indicting lights that illuminate when the detector activates. When smoke detectors are installed in any location not visible from the floor area, remote indicating lights shall be provided in a location approved by the city fire department.

d. The installation of safety guards over alarm initiating devices may be required when such devices are subject to damage or frequent malicious activation.

e. All sprinkler system control valves and associated control functions shall be equipped with electric supervision including pump power, pump run and room temperature etc. Supervised functions shall transmit a separate and distinct supervisory alarm. said alarm should automatically restore when the supervised function is restored to the normal position and indicates restoration at the remote alarm monitoring station.

f. Alarm system indicating panels shall be placed so that fire fighting personnel do not have to pass through or into the structure any further than the main entrance to view or operate the alarm panel.

 

(6) Vacant buildings. The alarm system shall remain in operation at all times.

 

(PDF version here)

Existing Buildings

The 2009 IEBC is made part of the Commercial Building Code, subject to the modifications specified in the Wis. Adm. Code § SPS 366.

Other Building Codes

The Wisconsin Electrical Code § SPS 316 (Based on the National Electrical Code, NFPA 70, 2011 edition).

The Wisconsin Plumbing Code Plumbing § SPS 380-387.

The International Energy Conservation Code, 2009 edition. Subject to modifications specified in § SPS 363.

The International Mechanical Code, 2009 edition. Subject to modifications specified in § SPS 364.

The International Fuel Gas Code, 2009 edition. Subject to modifications specified in § SPS 365.